ORVALDI VT6-10K (L) on-line

Seria: On-line

ORVALDI VT series is a high flexibility UPS with 2-in-1 design which integrates standard backup UPS and long-run UPS into one unit by simply adjusting charging current via LCD front panel. This high flexibility UPS offers easy-adjustable battery numbers design for diverse applications

Manufacturer: ORVALDI
Product code: VWPP6KL
ORVALDI VT6-10K (L) on-line
ORVALDI VT6-10K (L) on-line
ORVALDI VT6-10K (L) on-line
ORVALDI VT6-10K (L) on-line
ORVALDI VT6-10K (L) on-line

Characteristic:

  • True double-conversion on line UPS
  • DSP technology guarantees high performance
  • Output power factor 0.8
  • Standard backup UPS and long backup UPS in one integrated unit
  • Adjustable battery number from 16 pcs to 20 pcs
  • Adjustable charging current can be changed via LCD or software (1A~6A)
  • Wide input voltage range (110-300 VAC)
  • Active input power factor correction 0.99
  • 50Hz/60Hz frequency converter mode
  • Emergency power off function (EPO)
  • 3-stage extendable charging design for optimized battery performance
  • Maintenance bypass available
  • SNMP/USB/RS-232 communications

List of applications:

Medical equipment

Datacenters

Telecom hubs

Technical data:

Model ORVALDI V6K(L) on-line ORVALDI V6KR on-line ORVALDI V10K(L) on-line CoORVALDI V10KR on-line
Phase 1 phase in / 1 phase out
Capacity 6000 VA / 4800 W 10000 VA / 8000 W
INPUT
Frequency Range 46Hz ~ 54 Hz @ 50Hz system ; 56Hz ~ 64 Hz @ 60Hz system
Power Factor ≧ 0.99 @ 100% load
Voltage Range
Low Line Transfer 110 VAC ± 1% at 50% Load ; 176 VAC ± 1% at 100% Load
Low Line Comeback 120 VAC ± 1% at 50% Load ; 186 VAC ± 1% at 100% Load
High Line Transfer 300 VAC ± 3%
High Line Comeback 290 VAC ± 3%
OUTPUT
Nominal Voltage 208/220/230/240VAC
AC Voltage Regulation ± 1%
Frequency Range (Synchronized Range) 46Hz ~ 54 Hz @ 50Hz system ; 56Hz ~ 64 Hz @ 60Hz system
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1 (max.)
Waveform (Batt. Mode) Pure Sinewave
Harmonic Distortion ≦ 3 % THD (Linear Load), ≦ 6 % THD (Non-linear Load)
Transfer Time
Bypass to Inverter (Line mode) 0ms
Bypass to Inverter (ECO mode) 0ms
EFFICIENCY
Battery Mode 89%
Line Mode 90%
BATTERY
Standard Model
Battery Type 12 V / 9 AH 12 V / 9 AH 12 V / 9 AH 12 V / 9 AH
Numbers 16 16 20** (16-20 adjustable) 20** (16-20 adjustable)
Float Charging Voltage 218.4 VDC ± 1% 273 V DC± 1% (based on 20 pcs batteries)
Charging Current (max.) 1A ~ 6A ± 10% 1 A ± 10% 1A ~ 6A ± 10% 1.0 A ± 10%
Typical Recharge Time 9 hours recover to 90% capacity
Long-run Model
Battery Type Depending on applications
Numbers 16-20** (adjustable)
Charging Current (max.) 6.0 A ± 10% 2.0 A ± 10% 6.0 A ± 10% 2.0 A ± 10%
Float Charging Voltage 273 VDC ± 1% (based on 20 pcs batteries)
INDICATORS
LCD Display UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
ALARM
Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continuously sounding
PHYSICAL
Standard Model
Dimension, D x W x H (mm) 369 x 190 x 688 UPS Unit: 580x438x88 [2U] ; Battery Pack:580x438x133 [3U] 442 x 190 x 688 UPS Unit: 668x438x88[2U] ; Battery Pack:580x438x133[3U]
Net Weight (kgs) 60 UPS Unit: 15 ; Battery Pack: 48 75 UPS Unit: 18 ; Battery Pack: 63
Long-run Model
Dimension, D x W x H (mm) 369 x 190 x 318 580 x 438 x 88 [2U] 442 x 190 x 318 668 x 438 x 88[2U]
Net Weight (kgs) 21 15 23 18
ENVIRONMENT
Noise Level Less than 55dBA @ 1 Meter Less than 58dBA @ 1 Meter
Operating Temperature 0-95 % RH @ 0- 40°C (non-condensing)
MANAGEMENT
Optional SNMP Power management from SNMP manager and web browser
Smart RS-232/USB Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and MAC

*Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC.
**Power capacity will be derated while reducing battery number less than 20
***If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.
Product specifications are subject to change without further notice